Conference Record of 2010 Annual Pulp and Paper Industry Technical Conference

The paper demonstrates that in a multi-voltage level (medium and low-voltages) distribution system the incident energy can be reduced to 8 cal/cm2, or even less, (Hazard risk category, HRC 2), so that a PPE outfit of greater than 2 is not required. This is achieved with the current state of the art...

Ausführliche Beschreibung

Gespeichert in:
1. Verfasser:
IEEE Staff (MitwirkendeR)
Körperschaft:
Institute of Electrical and Electronics Engineers (IEEE)
Format:
Elektronisch E-Book
Sprache:
Englisch
Veröffentlicht:
[Place of publication not identified] IEEE 2010
Zusammenfassung:
The paper demonstrates that in a multi-voltage level (medium and low-voltages) distribution system the incident energy can be reduced to 8 cal/cm2, or even less, (Hazard risk category, HRC 2), so that a PPE outfit of greater than 2 is not required. This is achieved with the current state of the art equipment and protective devices. It is recognized that in the existing distribution systems, not specifically designed with this objective, it may not be possible to reduce arc flash hazard to this low level, unless major changes in the system design and protection are made. A typical industrial distribution system is analyzed, and tables and time coordination plots are provided to support the analysis. Unit protection schemes and practical guidelines for arc flash reduction are provided. The methodology of IEEE 1584 [1] is used for the analyses.
Umfang:
1 online resource : illustrations
Anmerkungen:
Bibliographic Level Mode of Issuance: Monograph
Anmerkungen:
English
ISBN:
9781424456772
1424456770
Schlagworte:
Bezugswerke:
Links: